Table 9-1 Trip indications
Trip
ACUU.P
Power module mains loss detection
101
Check AC supply level
C.Acc
SMARTCARD trip: SMARTCARD Read / Write fail
Check SMARTCARD is fitted / located correctly
185
Replace SMARTCARD
C.Chg
SMARTCARD trip: Data location already contains data
Erase data in data location
179
Write data to an alternative data location
SMARTCARD trip: The values stored in the drive and the values in the data block on the
C.Cpr
SMARTCARD are different
188
Press the red
C.dat
SMARTCARD trip: Data location specified does not contain any data
183
Ensure data block number is correct
C.Err
SMARTCARD trip: SMARTCARD data is corrupted
Ensure the card is located correctly
182
Erase data and retry
Replace SMARTCARD
C.Full
SMARTCARD trip: SMARTCARD full
184
Delete a data block or use different SMARTCARD
CL2
Analog input 2 current loss (current mode)
28
Check analog input 2 (terminal 7) current signal is present (0-20mA, 4-20mA etc.)
CL3
Analog input 3 current loss (current mode)
29
Check analog input 3 (terminal 8) current signal is present (0-20mA, 4-20mA etc.)
CL.bit
Trip initiated from the control word (Pr 6.42)
35
Disable the control word by setting Pr 6.43 to 0 or check setting of Pr 6.42
SMARTCARD trip: Solutions Modules fitted are different between source drive and
C.Optn
destination drive
Ensure correct Solutions Modules are fitted
180
Ensure Solutions Modules are in the same Solutions Module slot
Press the red
C.rdo
SMARTCARD trip: SMARTCARD has the Read Only bit set
Enter 9777 in Pr xx.00 to allow SMARTCARD Read / Write access
181
Ensure card is not writing to data locations 500 to 999