Safety
Product
Mechanical
Information
Information
Installation
Trip
ENP.Er
Data error from electronic nameplate stored in selected position feedback device
176
Replace feedback device
Et
External trip from input on terminal 31
Check terminal 31 signal
6
Check value of Pr 10.32
Enter 12001 in Pr xx.00 and check for parameter controlling Pr 10.32
Ensure Pr 10.32 or Pr 10.38 (=6) are not being controlled by serial comms
HF01
Data processing error: CPU address error
Hardware fault - return drive to supplier
HF02
Data processing error: DMAC address error
Hardware fault - return drive to supplier
HF03
Data processing error: Illegal instruction
Hardware fault - return drive to supplier
HF04
Data processing error: Illegal slot instruction
Hardware fault - return drive to supplier
HF05
Data processing error: Undefined exception
Hardware fault - return drive to supplier
HF06
Data processing error: Reserved exception
Hardware fault - return drive to supplier
HF07
Data processing error: Watchdog failure
Hardware fault - return drive to supplier
HF08
Data processing error: Level 4 crash
Hardware fault - return drive to supplier
HF09
Data processing error: Heap overflow
Hardware fault - return drive to supplier
HF10
Data processing error: Router error
Hardware fault - return drive to supplier
HF11
Data processing error: Access to EEPROM failed
Hardware fault - return drive to supplier
HF20
Power stage recognition: serial code error
220
Hardware fault - return drive to supplier
HF21
Power stage recognition: unrecognised frame size
221
Hardware fault - return drive to supplier
HF22
Power stage recognition: multi module frame size mismatch
222
Hardware fault - return drive to supplier
HF23
Power stage recognition: multi module voltage rating mismatch
223
Hardware fault - return drive to supplier
HF24
Power stage recognition: unrecognised drive size
224
Hardware fault - return drive to supplier
HF25
Current feedback offset error
225
Hardware fault - return drive to supplier
Soft start relay failed to close, soft start monitor failed or braking IGBT short circuit at
HF26
power up
226
Hardware fault - return drive to supplier
42
Electrical
Getting
Menu 0
Installation
Started
www.controltechniques.com
Running
Advanced
Diagnostics
the motor
parameters
Diagnosis
Unidrive SP Short Form Guide
UL Listing
Appendix
Information