Transmitter With Single-Compartment Housing - ABB ProcessMaster FEP300 Manual Del Usuario

Ocultar thumbs Ver también para ProcessMaster FEP300:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 219
6.4.2

Transmitter with single-compartment housing

„A"
1
2
3
Fig. 51: Jumpers in the single-compartment housing
A Integral mount design
B Remote mount design
1 Housing cover
2 Transmitter plug-in module
3 Fixing screws
4 Backplane (in the transmitter housing)
IMPORTANT (NOTE)
The backplane is mounted in the transmitter housing (not the transmitter plug-in module).
Configure the outputs as follows:
1. Switch off power supply.
2. Open the housing cover.
3. Remove the mounting screws for the transmitter electronics unit
4. Pull out the transmitter electronics unit
5. Set jumpers on backplane in accordance with the following table.
Jumper
BR901
BR902
BR903
BR904
BR905, BR906
6. Install the transmitter in reverse order.
CI/FEX300/FEX500-X1
6
„B"
5
3
Number
active
passive
Read only
integral
remote
active
passive
HART
PA/FF
4
5 Jumpers (BR905, BR906) for communication
6 Jumper (BR901) for active / passive current output
7 Jumper (BR904) for active / passive pulse output
8 Jumper (BR903) for integral / remote mount design
9 Jumper (BR902) for hardware write protection
Function
Current output 31 / 32 active
Current output 31 / 32 passive
Hardware write protection active
Transmitter with integral mount design
Transmitter with remote mount design
Pulse output 51 / 52 active
Pulse output 51 / 52 passive
Digital communication via HART protocol
Digital communication via PROFIBUS PA or
FOUNDATION Fieldbus
FEX300, FEX500
Commissioning
7
8
9
G01321
EN - 51

Publicidad

Tabla de contenido
loading

Tabla de contenido