Electrical connections
IMPORTANT (NOTE)
The cable with the part number D173D027U01 can be used for all device designs.
The cable with the part number D173D031U01 can be used for all device designs.
•
Sensor without explosion protection from nominal diameter DN 15 (models FEP321,
FEH321, FEP521, FEH521)
•
Sensor for use in Zone 2, Div. 2 from nominal diameter DN 15 (models FEP325, FEH325,
FEP525, FEH525)
IMPORTANT (NOTE)
Use wire end sleeves.
•
Wire end ferrules 0.75 mm
•
Wire end ferrules 0.5 mm
The shielding may not touch (signal short circuit).
Cable with part number D173D027U01
•
Uncover the braided shield of the cable and connect to the earth clamp together with the
earth wire
•
Connect all other wires as shown in Fig. 33
Cable with part number D173D031U01
•
Connect the earth wire of the cable together with the continuity wire of the foil shield from
D1, D2 to the earth clamp
•
Connect all other wires as shown in Fig. 33
36 - EN
2
(19 AWG), for shielding (1S, 2S)
2
(20 AWG), for all other wires
FEX300, FEX500
CI/FEX300/FEX500-X1