Electrical connections
5.7

Electrical data

5.7.1
Current / HART output
A
I
E
R
B
+31
-32
The current / HART output can be operated in "active" or "passive" mode.
Active: 4 ... 20 mA, HART protocol (standard), load: 250 Ω ≤ R ≤ 650 Ω
A
Passive: 4 ... 20 mA, HART protocol (standard), load: 250 Ω ≤ R ≤ 650 Ω
B
Supply voltage for the current output: minimum 11 V, maximum 30 V.
For Ex zone 1 / Div. 1 the maximum load is 300 Ω.
Fig. 39:
(I = internal, E = external)
5.7.2

Digital output DO1

A
I
E
19 ... 21 V+
51
-
52
The output can be configured as an "active (A)" or "passive (B)" output (in the case
of the transmitter with the dual-compartment housing, the output is configured
using the software; in the case of the transmitter with the single-compartment
housing, it is configured by means of jumpers on the transmitter backplane).
Configuration as "active" output:
U = 19 ... 21 V, Imax = 220 mA , fmax ≤ 5250 Hz
-
Configuration as "passive" output
Umax = 30 V, Imax = 220 mA, fmax ≤ 5250 Hz
-
Configuration as pulse output:
-
Max. pulse frequency: 5250 Hz.
-
Pulse width: 0.1 ... 2000 ms.
-
The pulse factor and pulse width are interdependent and are calculated
dynamically.
Configuration as contact output:
-
Function: System alarm, empty pipe alarm, max. / min. alarm, flow direction
signaling, other
Fig. 40:
(I = internal, E = external)
5.7.3

Digital output DO2

I
E
*
R
B
+U
+U
41
42
I
= 220 mA
max
U
*
R
CE
B
I
CE
Fig. 41:
(I = internal, E = external)
5.7.4

Digital input DI

I
E
Ri = 2 k
81
82
Fig. 42:
(I = internal, E = external)
42 - EN
B
I
E
R
B
V
+31
U
U
1
2
-32
B
I
E
51
52
I
= 220 mA
U
max
*
R
CE
B
I
CE
24V+
0V
FEX300, FEX500
700
650
600
550
500
G00475-01
450
400
350
300
250
200
17 18 19 20 21 22 23
Max. permissible load (R
voltage (U
2
1550
1450
1350
R
*
≤ 30 V+
B
1250
1150
U
1050
2
950
-
850
750
G00476-04
650
550
450
350
250
150
50
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Max. permissible load (R
voltage (U
2
The output is always a "passive" output (optocoupler).
Data for the optocoupler:
U
= 30 V, I
max
For maximum load see diagram Fig. 40.
G00792-01
Data for the optocoupler:
16 V ≤ U ≤ 30 V, Ri = 2 kΩ
G00477-01
24 25 26 27 28 29 30
U [V]
2
) as a function of the source
B
)
U [V]
2
) as a function of the source
B
).
= Permissible range

≤ 5250 Hz
= 220 mA, f
max
max
CI/FEX300/FEX500-X1