Cable length
Next
Exit
IMPORTANT (NOTE)
For additional information regarding operation of the LCD display, refer to chapter
"Operation".
For detailed descriptions of all menus and parameters, see chapter "Parameterization" of
the operating instruction.
CI/FEX300/FEX500-X1
Easy Setup
OK
Easy Setup
5.0000 m
Edit
Menu
Easy Setup
Select
FEX300, FEX500
43. Use
to start automatic balancing of the zero point
for the system.
IMPORTANT (NOTE)
Prior to starting the zero point balancing, make sure
that:
There is no flow through the sensor (close all
valves, shut-off devices etc.)
The sensor is completely filled with the medium to
be measured
Enter the signal cable length between the transmitter and
the sensor. For devices with an integral mount design
0.01 m must be entered.
44. Use
to call up the edit mode.
45. Use
or
to set the signal cable length.
46. Confirm the selection with
Once all parameter have been set, the main menu appears
again. The most important parameters are now set.
47. Use
to switch to the process display.
Commissioning
.
EN - 57