Control Panel
4.2.7 Menu 6: Maintenance Mode
By entering this menu, the user can change the UPS rated data, reset the EPO, clear the
event log, see the software and hardware version, configure the UPS activation from normal to
automatic and vice versa. This menu is password protected to prevent unauthorized access.
NOTE!
If the operator does not take any action for 3 minutes, menu "1. UPS STATUS
and ALARMS" is displayed automatically.
4.2.8 Battery Charging Current Adjustment
When powering up the equipment, it is necessary to adjust the battery bank capacity and the
value of the battery charging current.
Follow the procedure below:
1. Energize the equipment.
2. Via display, access menu 3 - Commands.
3. Access menu 3.6 - battery settings.
4. Access menu 3.6.1 - Battery capacity.
Adjust the battery capacity (Ah) according to the battery bank used with the product.
5. Access menu 3.6.2 - Max. charging current.
Adjust the battery charging current to the appropriate value. It is recommended that the
battery bank charging current be set to a value close to 0.1 C.
Example:
Battery bank capacity: 60 Ah.
Maximum charging current (0.1 C): 6 A.
38 | Enterprise