At this moment, if the backup line is in good condition, the load will be fed directly by the utility
company.
Open the main line switch-disconnector, DJE.
Close the manual bypass switch-disconnector, DJER.
Open the battery circuit breaker located on the UPS.
Open the UPS output switch-disconnector, DJS.
Open the backup line switch-disconnector, DJER.
Open the circuit breaker located on the battery bank.
After this procedure, contact the service center.
ATTENTION!
The batteries must no be disposed of with household, commercial or industrial
waste. They contain a toxic electrolyte harmful to human beings and the
environment. Dispose of the batteries according to CONAMA Resolution
401/08. When the battery life ends, send it to one of our authorized service
centers or contact WEG.
Preventive Maintenance
Enterprise | 59