7 PREVENTIVE MAINTENANCE
The UPS useful life is directly linked to scheduled/preventive maintenance processes, which
provide greater operational reliability and equipment efficiency. This type of maintenance must
be performed by the company that supplied the equipment or by a company that is specialized
and trained by the manufacturer.
7.1 ANNUAL MAINTENANCE (OR PERFORMED EVERY SIX MONTHS IN CAS-
ES OF MORE CRITICAL APPLICATIONS)
The following actions and tests are performed during the scheduled/preventive maintenance:
Clean the equipment.
Clean the control and interface boards.
Check the tightness of all nuts, screws and electrical connections (UPS and terminals of
each battery monoblock).
Test the ventilation efficiency.
Check the inverter output voltage wave form.
Check the output voltage and frequency.
Check the synchronism between the reserve line and the inverter output voltages.
Check the signals, alarms and actuation of the EPO.
Check the calibration of the Display with a calibrated instrument.
Test the operation of the manual switches and automatic devices.
Test the operation of the switching circuits.
Test energy fault on the UPS battery; test the efficiency of the battery.
Preventive Maintenance
Enterprise | 57