UPS Enterprise Parallelism Procedure
Turn off the inverter of UPS1 through the control panel and check if UPS2 has become the
MASTER and UPS1 has switched to SLAVE. Turn off the inverter of UPS1 again and check if
UPS2 continues as the MASTER and UPS1 as the SLAVE.
Check the exact relationship of the voltages at the outputs of the two units by measuring
the voltages at the UPS1 and UPS2 output switches. As the switches must be open, the
measurement must be made in the point before the disconnection.
L1-UPS1 = L1-UPS2.
L2-UPS1 = L2-UPS2.
L3-UPS1 = L3-UPS2.
N-UPS1 = N-UPS2.
Turn off the two inverters through the control panel and close the output circuit of both devices
(Figure 5.12 on page
44).
Mains
Res.
Mains
line
line
line
DJE
DJE
DJER
DJBP
UPS1
Manual
Bypass
DJS
Output
Output
Figure 5.12: Position of switch-disconnectors when the mains line and output switch-disconnectors closed
Turn of the inverters of UPS1 and UPS2. Check if the two units are operating in parallel from
this moment. Check if UPS1 is MASTER and UPS2 is SLAVE.
Close the UPS2 reserve input
that is, UPS2 becomes MASTER and UPS1 becomes SLAVE.
Mains
Res.
Mains
line
line
line
DJE
DJE
DJER
DJBP
UPS1
Manual
Bypass
DJS
Output
Output
Figure 5.13: Position of switch-disconnectors when mains line and output switch-disconnectors closed and UPS2 reserve line
44 | Enterprise
Res.
Mains
line
line
DJER
DJE
DJBP
UPS2
UPSn
Manual
Bypass
DJS
DJS
Output
(Figure 5.13 on page
Res.
Mains
line
line
DJE
DJER
DJBP
UPS2
UPSn
Manual
Bypass
DJS
DJS
Output
switch-disconnector closed
Res.
Mains line
line
DJER
ON
DJBP
Mains line
Manual
Bypass
ON
44). The configuration should reverse,
Res.
Mains line
line
DJER
ON
DJBP
Mains line
Manual
Bypass
ON
UPS 1
Reserve
M-Bypass
Output
OFF
OFF
ON
UPS 2
Reserve
M-Bypass
Output
OFF
OFF
ON
UPS 1
Reserve
M-Bypass
Output
OFF
OFF
ON
UPS 2
Reserve
M-Bypass
Output
ON
OFF
ON

Publicidad

loading