Technical Data
Temperature
Relative humidity
Noise level
Weight (kg) - without batteries
LCD display
Visible alarms
Acoustic alarm
SNMP
RS232 or RS485
Dry contact
Communication parallelism
Isolation transformer
Autotransformer
Note: The technical specifications contained in this catalog may undergo modifications without previous notice, as well as
they can be changed in order to meet the requirements of special orders and tender bids.
(1) Considering the maximum battery charging current.
(2) Other values on request.
Power (kVA)
Power (kW) - FP 0.8
Rated voltage
(2)
Maximum voltage variation
Rated frequency
Frequency range in operation
Configuration
Power factor
Max. input current (A)
- three-phase / single-
(1)
phase
Total harmonic distortion (THDi)
Starting ramp
Protections
Connection
Efficiency
Rated voltage
(2)
Rated output current (A)
Rated frequency
Frequency variation
Dynamic voltage regulation
Static voltage regulation
Total harmonic distortion (THDv)
Crest factor
Overload capacity
Protections
Connection
63 | Enterprise
Operation
58 dBA
70
Display
4 rows x 20 columns and 4 function buttons plus EPO pushbutton
Green LED (UPS OK); Red LED (UPS in alarm)
Communication
Service protocol or ModBus-RTU
250 Vac / 8 A (UPS in normal mode; UPS in bypass; input voltage present;
Optional items
Table 9.2: Technical specifications 220 Vac
10
8
Rectifier Input
220 Vac (three-phase) / 127 Vac (single-phase)
Three-phase (F+F+F+N) / single-phase (F+N)
45 / 120
Undervoltage, overvoltage, frequency variation, short circuit, EMI filter,
Inverter Output
220 Vac (three-phase) / 127 Vac (single-phase)
26.25 / 78.74
± 1 % or ± 2 % or ± 5 % or ± 10 % (adjustable)
< 3 % (linear load) / < 7 % (non-linear load)
Undervoltage, overvoltage, current limitation, overload, short circuit,
0 - 40 ºC (32 - 104 ºF)
< 95 % non-condensing
62 dBA
80
Standard
low battery)
Optical fiber
External enclosure
External enclosure
15
12
± 20 %
50/60 Hz
40/70 Hz
0.98
55 / 165
< 5 %
30 seconds
overtemperature
Terminal block
> 90 %
39.37 / 118
50 / 60 Hz
± 5 %
± 1 %
3:1
100 % - 125 % 10 min > 125 % 2 s
overtemperature
Terminal block
64 dBA
85
20
16
70 / 216
52.49 / 157