Rated voltage
Equalization voltage
Floating voltage
Minimum voltage
Number of batteries
Max. battery charging current (A)
Charging current limitation
Battery charge adjustable according to the
temperature compensation
Battery test
Rated voltage
Maximum voltage variation
Rated frequency
Allowable overload
Max. transfer times
Finishing
Color
Protection rating
Dimensions WxDxH (mm) [in]
Blower cooled
Temperature
Relative humidity
Noise level
Weight (kg) - without batteries
LCD display
Visible alarms
Acoustic alarm
SNMP
RS232 or RS485
Dry contact
Communication parallelism
Isolation transformer
Autotransformer
Note: The technical specifications contained in this catalog may undergo modifications without previous notice, as well as
they can be changed in order to meet the requirements of special orders and tender bids.
(1) Considering the maximum battery charging current.
(2) Other values on request.
Battery
12
Available by installing optional thermometer
Available/programmable
Bypass
220 Vac (three-phase) / 127 Vac (single-phase)
3 x In per 100 ms
Inverter to Bypass (Null) Bypass to Inverter (Null)
Overload or Fault (Null)
Manual Bypass (available with mechanical lock)
Steel frame
Politherm Powder Coating 23 R MT Black 73250 (11095031)
390 x 900 x 900 [15.35 x 35.43 x 35.43]
Operation
0 - 40 ºC (32 - 104 ºF)
< 95 % non-condensing
80
Display
4 rows x 20 columns and 4 function buttons plus EPO pushbutton
Green LED (UPS OK); Red LED (UPS in alarm)
Communication
Service protocol or ModBus-RTU
250 Vac / 8 A (UPS in normal mode; UPS in bypass; input voltage
present; low battery)
Optional items
External enclosure
External enclosure
Technical Data
432 Vdc
486 Vdc
486 Vdc
378 Vdc
36
10
10
Adjustable
± 20 %
50/60 Hz
IP20
400 m³/h
64 dBA
85
Standard
Fiber optic
Enterprise | 64