ELECTRIC CONTROL PANEL FOR THE EN12845 DIESEL FIRE-FIGHTING PUMP

9.1
General information
The control panel for the diesel fire-fighting pump installed as a standalone device or with other pressure
modules, was designed in compliance with the requirements of the fire-fighting standard UNI EN 12845.
The panel is also available in a version for fire-hydrant networks, characterized by the automatic shutting off of the pump after
the pressure has remained constantly above the starting pressure of the pump itself for the length of time specified by local
regulations (the default setting is 20 minutes).
9.2
Operating limits
Product in standard version.
Ambient storage temperature:
Ambient operating temperature:
Relative humidity:
Elevation:
Dusty environments with the presence of sand, or damp environments such as at the seaside, may
ATTENTION
cause premature deterioration, compromising regular operation.
For detailed characteristics refer to the documentation attached to the panel.
9.3

General technical data:

Alternating voltage:
Alternating frequency:
Max absorbed power:
Direct voltage of the batteries:
Dimensions:
Coating on structure:
Protection class:
The panels have already been programmed by the maker and must not be tampered with, unless
otherwise indicated by the maker. Incorrect unit programming can completely change machine
ATTENTION
operation and, in some cases, can cause serious harm to people or damage to property for which the
maker declines all liability.
1
2
RPM/H MODE
12.6
12.6
2900 AUTO
ALARM 63
01/01/2010
10.00.00
TEST
PROG
ENTER
2
7
6
P1
3
4
-10°C to 50 °C
+0°C to 45 °C
30% to 80% provided that no condensation occurs
max 1000 m ASL
1x230Vac +/-10%
50/60Hz
2500W
12 or 24Vdc +/-20% (selectable from the control unit)
500x350x200mm
RAL7035, not suitable for exposure to weathering
IP54 (optional IP55)
1 - Electric control unit
Display of alarms and status, battery voltage, speedometer, hour counter, alarm
programming, date display, main signals and manual start button.
2- Key-operated 3-position selector switch "Manual - Automatic- 0"
- "MAN" (MANUAL): Enabling of START/STOP/ENTER pushbuttons on the control
unit, with possibility of starting and stopping the engine. When the engine is
stopped, you can access the set-up configuration.
1
- "AUT" (AUTOMATIC): The motor is started via a pressure switch. Manual shut-
off, with the exception of UNI 10779 version for fire-hydrant networks.
6
- "0" (DISABLED): The diesel pump cannot be started manually or automatically
from the electronic control unit. The set up configuration can't be accessed in this
mode. Alarms can be reset using the RESET button for 5 sec, provided that the
P2
problem that triggered the alarm has been eliminated.
ON
3 (4) - Battery emergency start button 1(2)
This button starts the engine directly from battery 1 (2) in case of an emergency
5 - Main door-lock switch
Switch for the electrical power input of the panel
5
The diesel pump might start up because it is powered by the starting motor /
batteries
GF001_B_SC
6 – Warning lights of pressure switches
Indicating the state of the electrical contact of the pressure switch to pump start. If turned
on, the system pressure is belowe to PStart and the enginepump is running. In order to
the pump turns on is sufficient that at least one is active.
7 – Push button test lamp of pressure switches