Lowara GEMK Serie Instrucciones Para La Instalación Y El Uso página 121

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

9.13
ELECTRIC PANEL TERMINALS
X1 - TERMINALS FOR ANALOGUE AND DIGITAL INPUTS
CODE
DESCRIPTION
B1+
Battery 1 voltage value analogue signal input
B2+
Battery 2 voltage value analogue signal input
B-
Common input for the negative poles of batteries and other
AV1
Starting relay 1 control output
AV2
Starting relay 2 control output
STOP
Engine stopping device control output
"Low engine oil pressure" signal input. The controller enables the input 10 seconds after the engine starts up
BPO
"Engine overheating" signal input. The controller enables the input 10 seconds after the engine starts up
ATA
"Low fuel level" signal input
IN RIS.
CB
Engine battery charger current input
PK
Engine speed measurement pick-up frequency signal input
PK-
PICK-UP reference (ground)
PRESS-
Pressure switch starting contact signal reference (ground)
PRESS
Pressure switch starting contact signal input
IN AUX1
Digital signal enabled input, configurable in set-up
IN AUX2
Digital signal enabled input, configurable in set-up
IN AUX3
Digital signal enabled input. Available directly at the terminal block of the electronic control unit
MAN
Digital signal input for manual operation, available at the terminal block of the electronic control unit
0
Digital signal input for block operation control, available at the terminal block of the electronic control unit
Input for the supply of alternating current to the devices in the panel. It is obligatory to connect the phase,
QF1
neutral and ground (yellow/green) cables to the relative PE terminal
QU2
Output for the supply of alternating power to the heating device of the HEATER motor
RS232
Not available
121

Publicidad

Tabla de contenido
loading

Tabla de contenido