12. DECOMMISSIONING

The control unit and its panel contain electrical material. Observe the local rules on the recycling of waste.

13. ELECTRIC CONTROL PANEL FOR THE ELECTRIC JOCKEY PUMP

Data refer to standard-design product.
13.1
General
Electric panel for the electric jockey pump installed on pressure modules or provided as an additional kit. The motor is protected
against overload by an automatic switch.
Ready for connection to a float switch or minimum pressure switch for prevention of dry running. An optional level control
module (supplied on request) enables the connection of probes to electrodes with the possibility of adjusting sensitivity based on
water hardness.
A set of dry contacts is available on request for monitoring panel status
- Pump running.
- Thermal overload.
- No water.
1 - Signals
- Power supply voltage, white light.
1
- Thermal overload, red light.
- Pump running, green light.
2- 3-position selector switch "Manual - Automatic- 0"
- "MAN" (MANUAL):
2
- "AUT" (AUTOMATIC):
- "0" (DISABLED):
ON
3 - Main door-lock switch
Main door-lock switch which acts as a cut-off and emergency stop device.
It can be padlocked in its OFF position
3
GEN_0020_A_SC
starts the motor in manual mode.
Motor start-up and shut-off from pressure
switch.
Electric pump disabled.