ALARMS AND MESSAGES
The control unit has various alarms and messages.
DESCRIPTION
VISUAL.
Low engine oil
Display
pressure
High motor
Display
temperature
Low speed
Display
motor
"ESCAPE"
Display
overspeed
No Vac
alternating
Display
voltage
Low battery
Display
voltage
Switch not
Display +
automatic
Red LED
Display +
Failure to start
Red LED
Display +
Pump running
Red LED
Display +
Controller fault
Red LED
Fuel reserve
Display
Triggering of
protection of
Display
heater or battery
charger
Message
IN-AUX1,
Display
IN-AUX2,
IN-AUX3,
* Notes:
- With engine running: The control unit recognizes that the engine is running only when the revolution counter indicates a
number above 600 rpm; never edit the set "crown teeth" value.
- Engine status alarm: "Low engine oil pressure and overheating of engine" 10 seconds after the engine starts.
- No Vac voltage alarm, 1 second after measurement of the value.
- Low battery current alarm, 60 seconds after measurement of the value.
- Alarms can be reset using the RESET button for 5 sec, provided that the problem that triggered the alarm has been
eliminated.
IMPORTANT: all the alarms triggered during AUTOMATIC operation are only displayed on the screen and do not
disable the engine.
OUTPUT SIGNAL
Programmable relay + Alarm summary relay
Programmable relay + Alarm summary relay
Programmable relay + Alarm summary relay
Programmable relay + Alarm summary relay
Programmable relay + Alarm summary relay
Programmable relay + Alarm summary relay
Dedicated relay + alarm summary relay
Dedicated relay + alarm summary relay
Dedicated relay + alarm summary relay
Dedicated relay + alarm summary relay
Dedicated relay + alarm summary relay
Programmable relay + Alarm summary relay
Programmable relay + Alarm summary relay
ENABLE
With engine
running
With engine
running
With engine
running
With engine
running
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
Continuous
117
NOTES*
Permanent
Permanent
Permanent
Permanent
Permanent
Battery level low
12Vdc =alarm at 10Vdc
24Vdc =alarm at 22Vdc
Alarm triggered after 6 failed
attempts at automatic start-
up. Permanent
Permanent