From the fault buffer [8060.7]
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the fault buffer [8060.7]
<1> From the thermal monitoring, infeed
From the thermal monitoring, motor [8016.8]
From the thermal monitoring, power unit [8014.8]
From the thermal monitoring, motor [8016.8]
From the thermal monitoring, power unit [8014.8]
<1> Only for A_INFMV, B_INFMV, VECTORMV, VECTORSL.
1
2
DO: All objects
Internal control/status words - Status word, faults/alarms 1 and 2
Bit No.
Status word, faults/alarms 1
0
1 = Acknowledgement running
1
1 = Acknowledgement required
2
Reserved
3
1 = Fault present
4
Reserved
5
1 = Safety message present
6
1 = Internal message 1 present
7
1 = Alarm present
8
1 = Internal message 2 present
9
Reserved
10
Reserved
11
1 = Alarm class bit 0
12
1 = Alarm class bit 1
13
1 = Maintenance required
14
1 = Maintenance urgently required
15
1 = Fault gone/can be acknowledged
Bit No.
Status word, faults/alarms 2
0
1 = Fault encoder 1
1
1 = Fault encoder 2
2
1 = Fault encoder 3
3
...
Reserved
9
10
1 = Fault transformer overtemperature
[8770.6]
[8970.6]
11
1 = Alarm transformer overtemperature
12
1 = Fault motor overtemperature
13
1 = Fault power unit thermal overload
14
1 = Alarm motor overtemperature
15
1 = Alarm power unit thermal overload
3
4
r2139.0
r2139.1
r2139.3
r2139.5
r2139.6
r2139.7
r2139.8
r2139.11
r2139.12
r2139.13
r2139.14
r2139.15
r2135.0
r2135.1
r2135.2
<1>
r2135.10
r2135.11
<1>
r2135.12
r2135.13
r2135.14
r2135.15
5
6
Function diagram
fp_2548_51_eng.vsd
SINAMICS
18.02.14 V04.07.00
ZSW faults/alarms 1
Source sampling time
r2139
ZSW faults/alarms 2
r2135
<1>
<1>
7
8