p4108[0...5] = 1
Measuring
X53x.1
method
A
X53x.2
0: 1x2 wire
1: 2x2 wire
D
2: 3 wire
3: 4 wire
Cable R meas
Determine cable resistance
p4109[6...11]
(with short-circuited sensor)
x = 1, 2,
3, 4, 5, 6
p4119[6...11]
Measuring
method
A
0: 1x2 wire
X53x.3
1: 2x2 wire
D
X53x.4
2: 3 wire
3: 4 wire
Temperature evaluation
[9625]
Channel 6
...
Channel 11
<1> For p4102[0...23] = 251 °C the evaluation of the appropriate threshold is deactivated.
<2> p4100[0...11]
= 0: Evaluation deactivated
= 1: PTC thermistor (with monitoring for short-circuit)
= 2: KTY84 (with monitoring for wire break and short-circuit)
= 4: Bimetal NC contact (no monitoring)
= 5: PT100 (with monitoring for wire break and short-circuit)
= 6: PT1000 (with monitoring for wire break and short-circuit)
<3> For p4103 = 0 s and sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- The relevant fault can only be triggered via the fault threshold (the timer output is always logical 0).
For p4103 = 0 s and sensor type "PTC thermistor", "Bimetal NC contact" (p4100[0...11] = 1, 4) the following applies:
- The corresponding alarm and fault are output simultaneously (delay time = 0 s).
1
2
DO: TM150
Terminal Module 150 (TM150) - Temperature evaluation 2x2 wire (channels 0 ... 11)
Temperature evaluation
Channel 0
...
Channel 5
Save cable
resistance
R
PT1000
Calculate
resistance
+
R
PT100
0
1
50/60 Hz
R
Temp filt T
KTY84
r4120
PTC/
Bimetal
NC
p4121 (0)
contact
Filt f_line
Sensor R
r4101[6...11]
1650 Ÿ (PTC)
100 Ÿ (Bimetal)
3
4
[9626]
Cable R value
p4110[6...11]
p4102[12, 14, 16, 18, 20, 22] (251)
250 °C
T
-99 °C
Sensor type
250 °C
p4100[6...11]
<2>
T
PT1000
6
p4118[6...11] (5)
PT100
-99 °C
5
250 °C
Bimetal
4
KTY84
2
p4102[13, 15, 17, 19, 21, 23] (251)
T
PTC
1
0
-99 °C
-300 °C
1
0
1
0
250 °C
-50 °C
-300 °C
5
fp_9627_51_eng.vsd
04.12.12 V04.07.00
Alarm threshold
-99...251 [°C]
"Channel y alarm is present"
<1>
0.0...600.0 [s]
r4104.12
p4103[6...11] (0.0)
r4104.14
<3>
1
r4104.16
T
0
r4104.18
0
r4104.20
r4104.22
"Channel y fault is present"
1
Fault threshold
-99...251 [°C]
r4104.13
r4104.15
<1>
r4104.17
1
r4104.19
r4104.21
only for
0
KTY84, PT100,
r4104.23
PT1000
A35926 ... A35931
"Error temperature sensor channel y"
(y = 6 ... 11)
Temperature actual value
0
Alarm is present
1
6
7
Function diagram
SINAMICS
26000.00 μs
A35412 (Channel 6)
A35413 (Channel 7)
A35414 (Channel 8)
A35415 (Channel 9)
A35416 (Channel 10)
A35417 (Channel 11)
F35402 (Channel 6)
F35403 (Channel 7)
F35404 (Channel 8)
F35405 (Channel 9)
F35406 (Channel 10)
F35407 (Channel 11)
Temp act value
r4105[6...11]
Group formation
[9625.6]
8
- 9627 -

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sinamics g150

Tabla de contenido