SI status Control Unit
Bit
Meaning
No.
[2810.7]
0
1 = STO selected on Control Unit
[2811.6]
1
1 = STO active on Control Unit
1 = SS1 delay time active on the
[2810.5]
2
Control Unit
...
Reserved
[2814.3]
4
1 = SBC requested
1 = SS1 selected on the Control Unit
[2814.4]
5
(Basic Functions)
1 = SS1 active on the Control Unit
[2814.5]
6
(Basic Functions)
1 = STO Terminal state on the Motor
[2810.4]
7
Module (Basic Functions)
...
Reserved
1 = STOP A cannot be
[2802.7]
9
acknowledged, active
[2802.8]
10
1 = STOP A active
...
Reserved
[2802.5]
15
1 = STOP F active
[2810.6]
16
1 = STO cause Safety comm. mode
1 = STO cause selection via
[2810.5]
17
terminal (Basic Functions)
[2810.4]
18
1 = STO cause selection via SMM
1 = STO cause actual value or safe
[2819.8]
19
torque off missing
1 = STO cause selection PROFIsafe
[2810.6]
20
(Basic Functions)
...
Reserved
1 = SS1 cause selection terminal
[2810.4]
22
(Basic Functions)
1 = SS1 cause selection PROFIsafe
[2810.4]
23
(Basic Functions)
...
Reserved
1
2
DO: SERVO, VECTOR
SI Basic functions - SI status CU, MM, CU + MM, group STO
SI status Motor Module
SI status CU
Bit
Meaning
r9772
No.
[2810.7]
0
1 = STO on Motor Module selected
[2811.3]
1
1 = STO on Motor Module active
[2810.5]
2
1 = SS1 delay time on Motor Module active
3
1 = Safe Brake Adapter feedback signal
[2814.3]
4
1 = SBC requested
[2814.4]
5
1 = SS1 selected on the Motor Module (Basic Functions)
[2814.5]
6
1 = SS1 active on the Motor Module (Basic Functions)
[2810.4]
7
1 = STO Terminal state on the MM (Basic Functions)
...
Reserved
[2802.7]
9
1 = STOP A cannot be acknowledged, active
[2802.8]
10
1 = STOP A active
...
Reserved
[2802.5]
15
1 = STOP F active
[2810.6]
16 1 = STO cause: Safety comm. mode
[2810.5]
17 1 = STO cause selection via terminal (Basic Functions)
[2810.4]
18 1 = STO cause: selection via SMM
...
Reserved
[2810.6]
20 1 = STO cause selection PROFIsafe (Basic Functions)
...
Reserved
[2810.3]
22 1 = SS1 cause selection terminal (Basic Functions)
[2810.4]
23 1 = SS1 cause selection PROFIsafe (Basic Functions)
[2802.3]
24 1 = Slave Motor Module ready for communication
...
Reserved
3
4
SI status Control Unit + Motor Module
SI status MM
Bit
r9872
No.
&
0
1 = STO selected in drive
&
1
1 = STO active in drive
&
2
1 = SS1 delay time active in the drive
...
Reserved
&
4
1 = SBC requested
1 = SS1 selected in the drive (Basic
&
5
Functions)
1 = SS1 active in the drive (Basic
&
6
Functions)
...
Reserved
[2810.5]
31 1 = Shutdown paths must be tested
Status Safe Torque Off group
Bit
No.
r9773.0
&
0
1 = STO selected in group
Group n
r9773.1
&
1
1 = STO active in group
Group n
r9773.2
&
2
1 = SS1 delay time active in group
Group n
...
Reserved
r9773.4
&
4
1 = SBC requested in group
Group n
r9773.5
1 = SS1 selected in group (Basic
&
5
Functions)
Group n
r9773.5
1 = SS1 active in group (Basic
&
6
Functions)
Group n
...
Reserved
r9773.31
1 = Shutdown paths of the group
&
31
Group n
must be tested
5
6
Function diagram
fp_2804_54_eng.vsd
S120/S150/G130/G150
14.11.13 V04.07.00
r9780 CU/r9880 MM
SI status CU+MM
Meaning
r9773
SI stat group STO
Meaning
r9774
7
8
- 2804 -