p0115[3] (Drive Object)
Ramp-function generator selection
RFG selection
p1115
n_set_4
[3060.8]
0
n_set_5
[3070.8]
1
Torque limit reached
[2522.7]
r1407.7
<1>
For p1145 > 0, ramp-function generator tracking is activated when the
torque limiting responds. This means that the speed controller output only exceeds the torque limit by a
deviation that can be set via p1145.
<2>
For OFF1/OFF3, the ramp-function generator ramp is active. The ramp-function generator is set (SERVO: to the
actual value, VECTOR, VECTOR3P, VECTORGL, VECTORMV, VECTORSL: to the setpoint (r1170)) and stops
the drive with the ramp-downtime (p1121 or p1135). STW1.4 (enable ramp-function generator) is effective while
the drive is stopped via the ramp-function generator. Depending on the p1115, the basic ramp-function
generator [3060] or the extended ramp-function generator [3070] is effective.
For SERVO is valid: When the function module "extended setpoint channel" is not active (r0108.8 = 0), for
OFF1/OFF3 the down ramp of the basic ramp-function generator is effective (refer to n_set_4 on [3060.8]).
<3>
The interpolator is only active with activated "basic positioner" Function Module or with isochronous PROFIdrive
mode and sign of life received by the master (STW2.12 ... STW2.15).
<4>
Behavior of the response ramp of the torque limiting:
p1145 = 0.0: No ramp-function generator tracking. The ramp-function generator ramp is no longer in the range
of the speed actual value.
p1145 = 1.0: The ramp-function generator ramp remains as close as possible to the speed actual value.
p1145 > 1.0: The ramp-function generator ramp is steeper than for p1145 = 1.0 (higher "speed following error").
<5>
The value is displayed correctly only with r0899.2 = 1 (Operation enabled).
<6>
For SERVO only.
<7>
For VECTOR, VECTOR3P, VECTORMV only.
<8>
For VECTORGL only.
<101> To view the pre-assignment of the sampling times in p0115, refer to p0112.
1
2
DO: SERVO, VECTOR, VECTOR3P, VECTORGL, VECTORM2C, VECTORMV, VECTORSL
Setpoint channel - Ramp-function generator selection, status word, tracking
Enable ramp-function generator
r0898.4
From the
Enable speed setpoint
STW
r0898.6
Jog 1
sequence
r0898.8
control
Jog 2
[2501.7]
r0898.9
n_ctrl n_set 1
p1155[C]
<2>
(0)
<2>
n_ctrl n_set 2
p1160[C]
(0)
f_set
[9816.7]
0
<8>
0
Sync f_corr [Hz]
[7020.8]
r3812
<7>
1
Synchronization
No OFF1
&
No OFF2
No OFF3
RFG n_set at outp
RFG track intens
0.0...50.0
r1150
p1145[D] (1.3)
p1151.1 p1151.2
3
4
&
p1189.1
1
x,y
0
x
0
+
1
+
+
0
Interpolator
Not SERVO or
p1189.0
r0108.8 = 1 (Extend setp)
x,y
T1
x
0
1
0
1
0
Interpolator
<4>
Ramp-function generator tracking
Ramp-function generator status word
[3060.8]
Bit
Ramp-function generator status word
[3070.8]
0
Ramp-up active
[3060.8]
1
Ramp-down active
[3070.8]
2
Ramp-function generator active
1
3
Ramp-function generator set
4
Ramp-function generator held
[3080.8]
5
Ramp-function generator tracking active
[3050.8]
6
Maximum limiting active
7
Ramp-function generator speedup positiv
8
Ramp-function generator speedup negativ
9
Reserved
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
5
6
fp_3080_51_eng.vsd
16.10.13 V04.07.00
p0115[1] (Drive Object)
<101>
n_ctrl n_set 1/2
r1169
<5>
<3>
Friction char. Record
x
T1
y
No OFF2
y
&
No OFF3
t
+
0
n_ctrl setp sum
x
r1170
+
y
y
<5>
1
From the ramp-function
t
generator friction characteristic
[7010.6]
Ramp flattening-off
Ramp-function generator tracking active
r1199.5
RFG ZSW
r1199
r1199.0
r1199.2
r1199.3
<1>
r1199.5
7
Function diagram
SINAMICS
[3050.1]
[5020.1] <6>
[6030.1]
[8011.2]
[3060.1]
<4>
[3070.3]
[6300.1]
[6726.4]
[6031.1]
[6031.1]
8
- 3080 -