Siemens SINAMICS G130 Manual De Listas página 1028

Ocultar thumbs Ver también para SINAMICS G130:
Tabla de contenido

Publicidad

Changing the fault response for maximum 20 faults <1>
p2100
[0]
0. Fault code
[0]
[1]
1. Fault code
[1]
[19]
19. Fault code
[19]
Changing the acknowledge mode for maximum 20 faults <1>
p2126
[0]
0. Fault code
[0]
[1]
1. Fault code
[1]
[19]
19. Fault code
[19]
<1> The fault response, acknowledge mode and message type for all faults and alarms are set to meaningful default values in the factory setting.
Changes that may be required are only possible in specific value ranges specified by SIEMENS.
When the message type is changed, the supplementary information is tranferred from fault value r0949 to alarm value r2124 and vice versa.
1
2
DO: All objects
Diagnostics - Fault/alarm configuration
p2101
Fault response
0 = NONE
Fault response
1 = OFF1
2 = OFF2
3 = OFF3
4 = STOP1
5 = STOP2
6 = IASC/DCBRAKE
7 = ENCODER (p0491)
Fault response
p2127
Acknowledge mode
1 = Acknowledgment is only possible using POWER ON
Acknowledge mode
2 = Acknowledgment IMMEDIATELY after the cause has been removed.
3 = Acknowledge only when the PULSES ARE INHIBITED.
Acknowledge mode
3
4
Changing the message type - fault <==> alarm for maximum 20 faults/alarms <1>
p2118
[0]
0. Fault/alarm code
[1]
1. Fault/alarm code
[19]
19. Fault/alarm code
5
6
fp_8075_51_eng.vsd
07.09.09 V04.03.01
Background
Refer to [1020.7]
p2119
[0]
Fault/alarm type
1 = Fault (F)
[1]
Fault/alarm type
2 = Alarm (A)
3 = No message(N)
[19]
Fault/alarm type
7
8
Function diagram
- 8075 -
SINAMICS

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sinamics g150

Tabla de contenido