Signal targets for A_DIGITAL
Signal
Meaning
A_DIGITAL.0
Digital output 8 (DI/DO 8)
A_DIGITAL.1
Digital output 9 (DI/DO 9)
A_DIGITAL.2
Digital output 10 (DI/DO 10)
A_DIGITAL.3
Digital output 11 (DI/DO 11)
A_DIGITAL.4
Digital output 12 (DI/DO 12)
A_DIGITAL.5
Digital output 13 (DI/DO 13)
A_DIGITAL.6
Digital output 14 (DI/DO 14)
A_DIGITAL.7
Digital output 15 (DI/DO 15)
A_DIGITAL.8
Reserved
A_DIGITAL.9
Reserved
A_DIGITAL.10
Reserved
A_DIGITAL.11
Reserved
A_DIGITAL.12
Reserved
A_DIGITAL.13
Reserved
A_DIGITAL.14
Reserved
A_DIGITAL.15
Reserved
<1> Used in telegrams 390, 391 and 392.
1
2
DO: CU_G, CU_S
PROFIdrive - A_DIGITAL interconnection
Interconnection
parameters
<2>
p0738[0] = r2091[0]
<2>
p0739[0] = r2091[1]
p0740[0] = r2091[2]
<2>
<2>
p0741[0] = r2091[3]
<2>
p0742[0] = r2091[4]
<2>
p0743[0] = r2091[5]
p0744[0] = r2091[6]
<2>
p0745[0] = r2091[7]
<2>
<2> Can be set via p0728 as input (DI) or output (DO).