Setting The Data Rate; Setting The Bus Coupler Address - Aventics CANopen VS CL03 Serie Instrucciones De Servicio

Ocultar thumbs Ver también para CANopen VS CL03 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 223
82
AVENTICS | CANopen | R402003660–BAL–001–AE
Commissioning and operation
S1
S2
7.1.1

Setting the data rate

Set the data rate (baud rate) with the switches S3.1 to S3.3
in accordance with the information listed in Table 8 below.
Default setting: 1 Mbit/s
Table 8:
Switch assignment for data rate setting
Data rate
Max. wire length
1 Mbit/s
25 m
Reserved
500 kbit/s
100 m
250 kbit/s
250 m
125 kbit/s
500 m
50 kbit/s
1 km
20 kbit/s
2.5 km
10 kbit/s
5 km
7.1.2

Setting the bus coupler address

The station address is set using switches S1 and S2.
Changes during operation
Changes to the addressing are only activated after a power
reset.
Never change the settings during operation.
Turn the device off before changing the address setting.
Assign the station address freely from 1 to 99 using S1 and S2.
– S1: Unit digits from 0 to 9
– S2: Tens digits from 0 to 9
– [S2] [S1] = Station address
Default setting: node ID = 02
Do not use address 0, it causes a system stop.
S3.3
ON
ON
ON
ON
OFF
OFF
OFF
OFF
CAUTION
S3.2
S3.1
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF

Publicidad