S3
ON
OFF
Table 9:
S3, Setting diagnostic messages
Switch
Setting
S3.5
OFF (default)
ON
S3
ON
OFF
Table 10:
S3, Setting the valve supply tolerance threshold
Switch
Setting
S3.4
OFF (default)
ON
AVENTICS | CANopen | R402003660–BAL–001–AE
7.1.3

Setting diagnostic messages

To select diagnostic messages the S3 DIP switch, position 5, is
used.
At delivery, all switches are set to the OFF position. That is,
no diagnostic messages are sent to the bus master (S3.5
switch position OFF).
Activate diagnostic messages by setting the S3.5 switch
position ON.
Changes will be activated after a power reset.
This setting can also be assigned using the Module Control
Register. If assigned via the Module Control Register, bit 3,
the position of switch S3.5 is irrelevant.
The queued diagnoses are shown on the LEDs even if the
diagnostic message is turned off on the master.
Function
Diagnostic messages deactivated
Diagnostic messages activated
7.1.4

Setting tolerance level for valve supply U

and U
Q2
The threshold for valve supply U
different valve series with the S3 switch, position 4. At delivery,
the threshold is set to 21.6 V (–10%)(S3.4set to OFF), but can be
changed to 20.4 V (–15%)(S3.4 set to ON).
If the valve supply voltage drops below this threshold, a
diagnostic message will be generated.
Function
Threshold for U
Threshold for U
Commissioning and operation
and U
can be adjusted for
Q1
Q2
and U
is 21.6 V (–10%)
Q1
Q2
and U
is 20.4 V (–15%)
Q1
Q2
83