Programming and Parameters
Basic Program Group
Stop drive before changing this parameter.
P031 [Motor NP Volts]
Set to the motor nameplate rated volts.
Values
Default
Min/Max:
Display:
Stop drive before changing this parameter.
P032 [Motor NP Hertz]
Set to the motor nameplate rated frequency.
Values
Default
Min/Max:
Display:
P033 [Motor OL Current]
Set to the maximum allowable motor current.
The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60
seconds or 200% for 3 seconds.
Values
Default
Min/Max:
Display:
P034 [Minimum Freq]
Sets the lowest frequency the drive will output continuously.
Values
Default
Min/Max:
Display:
Stop drive before changing this parameter.
P035 [Maximum Freq]
Sets the highest frequency the drive will output.
Values
Default
Min/Max:
Display:
Based on Drive Rating
20/Drive Rated Volts
1 VAC
60 Hz
10/240 Hz
1 Hz
Related Parameter(s): A089, A090,
Based on Drive Rating
0.0/(Drive Rated Amps × 2)
0.1 Amps
0.0 Hz
0.0/240.0 Hz
0.1 Hz
60 Hz
0/240 Hz
1 Hz
Related Parameter(s):
Related
Parameter(s):A084
Related Parameter(s):
Related Parameter(s):
A084
A098
P035