Start Up
This chapter describes how to start up the PowerFlex 40 Drive. To
simplify drive setup, the most commonly programmed parameters are
organized in a single Basic Program Group.
Important: Read the General Precautions section before proceeding.
ATTENTION: Power must be applied to the drive to perform the
following start-up procedures. Some of the voltages present are at
!
incoming line potential. To avoid electric shock hazard or damage to
equipment, only qualified service personnel should perform the
following procedure. Thoroughly read and understand the procedure
before beginning. If an event does not occur while performing this
procedure, Do Not Proceed. Remove All Power including user
supplied control voltages. User supplied voltages may exist even when
main AC power is not applied to the drive. Correct the malfunction
before continuing.

Prepare For Drive Start-Up

Before Applying Power to the Drive
1. Confirm that all inputs are connected to the correct terminals and are
secure.
2. Verify that AC line power at the disconnect device is within the rated
value of the drive.
3. Verify that any digital control power is 24 volts.
4. Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to
match your control wiring scheme. See
location.
Important: The default control scheme is Source (SRC). The Stop
5. Verify that the Stop input is present or the drive will not start.
Important: If I/O Terminal 01 is used as a stop input, the jumper
terminal is jumpered (I/O Terminals 01 and 11) to allow
starting from the keypad. If the control scheme is changed
to Sink (SNK), the jumper must be removed from I/O
Terminals 01 and 11 and installed between I/O Terminals
01 and 04.
between I/O Terminals 01 and 11 must be removed.