3-10
Programming and Parameters
Basic Program Group
P036 [Start Source]
Stop drive before changing this parameter.
Sets the control scheme used to start the drive.
Refer to
Start and Speed Reference Control on page 1-20
can override the setting of this parameter.
Important: For all settings except option 3, the drive must receive a leading edge from the start input
for the drive to start after a stop input, loss of power or fault condition.
Options 0 "Keypad" (Default)
1 "3-Wire"
2 "2-Wire"
3 "2-W Lvl Sens"
!
4 "2-W Hi Speed"
5 "Comm Port"
• Integral keypad controls drive operation.
• I/O Terminal 1 "Stop" = coast to stop.
• When active, the Reverse key is also active unless
disabled by
I/O Terminal 1 "Stop" = stop according to the value set
in
P037
I/O Terminal 1 "Stop" = coast to stop.
Drive will restart after a "Stop" command when:
• Stop is removed
and
• Start is held active
ATTENTION: Hazard of injury exists due to unintended operation. When
P036 [Start Source] is set to option 3, and the Run input is maintained, the
Run inputs do not need to be toggled after a Stop input for the drive to run
again. A Stop function is provided only when the Stop input is active (open).
Important: There is greater potential voltage on the output
terminals when using this option.
• Outputs are kept in a ready-to-run state. The drive will
respond to a "Start" command within 10 ms.
• I/O Terminal 1 "Stop" = coast to stop.
• Remote communications. Refer to Appendix C for details.
• I/O Terminal 1 "Stop" = coast to stop.
(continued)
Related Parameter(s): d012,
for details about how other drive settings
A095
[Reverse Disable].
[Stop Mode].
P037