Advanced Program Group
A058 [Opto Out1 Sel]
A061 [Opto Out2 Sel]
Determines the operation of the programmable opto outputs.
Options 0 "Ready/Fault"
1 "At Frequency"
(A061 Default)
2 "MotorRunning"
(A058 Default)
3 "Reverse"
4 "Motor Overld"
5 "Ramp Reg"
6 "Above Freq"
7 "Above Cur"
8 "Above DCVolt"
9 "Retries Exst"
10 "Above Anlg V"
11 "Logic In 1"
12 "Logic In 2"
13 "Logic 1 & 2"
14 "Logic 1 or 2"
15 "StpLogic Out"
16 "Timer Out"
17 "Counter Out"
Programming and Parameters
(continued)
Related Parameter(s): P033, A056, A092, A140-A147,
Opto outputs are active when power is applied. This indicates
that the drive is ready for operation. Opto outputs are inactive
when power is removed or a fault occurs.
Drive reaches commanded frequency.
Motor is receiving power from the drive.
Drive is commanded to run in reverse direction.
Motor overload condition exists.
Ramp regulator is modifying the programmed accel/decel
times to avoid an overcurrent or overvoltage fault from
occurring.
• Drive exceeds the frequency (Hz) value set in
A062
[Opto Outx Level].
• Use A059 or A062 to set threshold.
• Drive exceeds the current (% Amps) value set in
A062
[Opto Outx Level].
• Use A059 or A062 to set threshold.
Important: Value for
entered in percent of drive rated output current.
• Drive exceeds the DC bus voltage value set in
A062
[Opto Outx Level].
• Use A059 or A062 to set threshold.
Value set in
A092
• Analog input voltage (I/O Terminal 13) exceeds the value
set in
A056
[Relay Out Level].
• Do not use if
A123
In".
• This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 13) is wired to a
PTC and external resistor.
• Use A056 to set threshold.
An input is programmed as "Logic In 1" and is active.
An input is programmed as "Logic In 2" and is active.
Both Logic inputs are programmed and active.
One or both Logic inputs are programmed and one or both is
active.
Drive enters Step Logic step with Digit 3 of Command Word
(A140
- A147) set to enable Step Logic output.
• Timer has reached value set in
Level].
• Use A059 or A062 to set threshold.
• Counter has reached value set in
Outx Level].
• Use A059 or A062 to set threshold.
A059
or
A062
[Opto Outx Level] must be
[Auto Rstrt Tries] is exceeded.
[10V Bipolar Enbl] is set to 1 "Bi-Polar
A059
A059
3-17
A150-A157
A059
or
A059
or
A059
or
or
A062
[Opto Outx
or
A062
[Opto