Writing (06) Logic Command Data
The PowerFlex 4 drive can be controlled via the network by sending
Function Code 06 writes to register address 8192 (Logic Command).
P036 [Start Source] must be set to 5 "RS485 (DSI) Port" in order to
accept the commands.
Address (Decimal) Bit(s)
0
1
2
3
5,4
6
7
9,8
8192
11,10
14,13,12
15
Writing (06) Reference
The Speed Reference to a PowerFlex 4 drive can be controlled via the
network by sending Function Code 06 writes to register address 8193
(Reference). P038 [Speed Reference] must be set to 5 "RS485 (DSI)
Port" in order to accept the Speed Reference.
Address (Decimal) Description
A decimal value entered as xxx.x where the decimal point is fixed. For
8193
example, a decimal "100" equals 10.0 Hz and "543" equals 54.3 Hz.
RS485 (DSI) Protocol
Logic Command
Description
1 = Stop, 0 = Not Stop
1 = Start, 0 = Not Start
1 = Jog, 0 = No Jog
1 = Clear Faults, 0 = Not Clear Faults
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Change Direction (Toggle)
Not Used
Not Used
00 = No Command
01 = Accel Rate 1 Enable
10 = Accel Rate 2 Enable
11 = Hold Accel Rate Selected
00 = No Command
01 = Decel Rate 1 Enable
10 = Decel Rate 2 Enable
11 = Hold Decel Rate Selected
000 = No Command
001 = Freq. Source = P036 [Start Source]
010 = Freq. Source = A069 [Internal Freq]
011 = Freq. Source = Comms (Addr 8193)
100 = A070 [Preset Freq 0]
101 = A071 [Preset Freq 1]
110 = A072 [Preset Freq 2]
111 = A073 [Preset Freq 3]
Not Used
Reference
C-3