1-2
Installation/Wiring
Mounting Considerations
• Mount the drive upright on a flat, vertical and level surface.
Frame
B
C
• Protect the cooling fan by avoiding dust or metallic particles.
• Do not expose to a corrosive atmosphere.
• Protect from moisture and direct sunlight.
Minimum Mounting Clearances
Refer to
120 mm
(4.7 in.)
120 mm
(4.7 in.)
Ambient Operating Temperatures
Table 1.A Enclosure and Clearance Requirements
Ambient Temperature
Minimum
-10°C (14°F)
(1)
Rating requires installation of the PowerFlex 40 IP 30/NEMA 1/UL Type 1 option kit.
Debris Protection
A plastic top panel is included with the drive. Install the panel to prevent
debris from falling through the vents of the drive housing during
installation. Remove the panel for IP 20/Open Type applications.
Storage
• Store within an ambient temperature range of -40° to +85°C.
• Store within a relative humidity range of 0% to 95%,
non-condensing.
• Do not expose to a corrosive atmosphere.
Screw Size
M4 (#8-32)
M5 (#10-24)
Appendix B
for mounting dimensions.
Mounting Option B
Enclosure Rating
Maximum
IP 20/Open Type
40°C (104°F)
IP 30/NEMA 1/UL Type 1
50°C (122°F) IP 20/Open Type
Screw Torque
1.56-1.96 N-m (14-17 lb.-in.)
2.45-2.94 N-m (22-26 lb.-in.)
Mounting Option A
No clearance required
between drives.
(1)
DIN Rail
35 mm
–
25 mm
(1.0 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
Minimum Mounting
Clearances
Use Mounting Option A
Use Mounting Option B
Use Mounting Option B