1-12
Installation/Wiring
Table 1.E Power Terminal Block Specifications
Frame
B
C
(1)
Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.
I/O Wiring Recommendations
Motor Start/Stop Precautions
ATTENTION: A contactor or other device that routinely disconnects
and reapplies the AC line to the drive to start and stop the motor can
!
cause drive hardware damage. The drive is designed to use control input
signals that will start and stop the motor. If used, the input device must
not exceed one operation per minute or drive damage can occur.
ATTENTION: The drive start/stop control circuitry includes
solid-state components. If hazards due to accidental contact with
!
moving machinery or unintentional flow of liquid, gas or solids exist,
an additional hardwired stop circuit may be required to remove the AC
line to the drive. When the AC line is removed, there will be a loss of
any inherent regenerative braking effect that might be present - the
motor will coast to a stop. An auxiliary braking method may be
required.
Important points to remember about I/O wiring:
• Always use copper wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control and signal wires should be separated from power wires by at
least 0.3 meters (1 foot).
Important: I/O terminals labeled "Common" are not referenced to the
ATTENTION: Driving the 4-20mA analog input from a voltage
source could cause component damage. Verify proper configuration
!
prior to applying input signals.
(1)
Maximum Wire Size
2
5.3 mm
(10 AWG)
2
8.4 mm
(8 AWG)
safety ground (PE) terminal and are designed to greatly
reduce common mode interference.
(1)
Minimum Wire Size
2
1.3 mm
(16 AWG)
2
1.3 mm
(16 AWG)
Torque
1.7-2.2 N-m (16-19 lb.-in.)
2.9-3.7 N-m (26-33 lb.-in.)