A111 [0-10V Analog Input High]
Sets the analog input level that corresponds to P035 [Maximum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than A110 [0-10V Analog Input
Low].
Values
Default
Min/Max:
Display:
A112 [4-20mA Analog Input Low]
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 4-20mA input is used by
P038 [Speed Reference].
Analog inversion can be accomplished by setting this value larger than A113 [4-20mA Analog Input
High].
Values
Default
Min/Max:
Display:
A113 [4-20mA Analog Input High]
Sets the analog input level that corresponds to P035 [Maximum Freq] if a 4-20mA input is used by
P038 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than A112 [4-20mA Analog Input
Low].
Values
Default
Min/Max:
Display:
A114 [Slip Compensation]
Compensates for the inherent slip in an induction motor. This frequency is added to the commanded
output frequency based on motor current.
Values
Default
Min/Max:
Display:
Programming and Parameters
Related Parameter(s): d020, P035,
100.0%
0.0/100.0%
0.1%
Related Parameter(s): d021, P034,
0.0%
0.0/100.0%
0.1%
Related Parameter(s): d021, P035,
100.0%
0.0/100.0%
0.1%
2.0 Hz
0.0/10.0 Hz
0.1 Hz
P038
P038
P038
Related Parameter(s):
3-25
P033