Advanced Program Group
A092 [Auto Rstrt Tries]
Sets the maximum number of times the drive attempts to reset a fault and restart.
Clear a Type 1 fault and restart the drive.
1. Set A092 [Auto Rstrt Tries] to a value other than "0".
2. Set A093
[Auto Rstrt Delay]
Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault without restarting the drive.
1. Set A092 [Auto Rstrt Tries] to a value other than "0".
2. Set A093
[Auto Rstrt Delay]
ATTENTION: Equipment damage and/or personal injury may result if this parameter
is used in an inappropriate application. Do not use this function without considering
!
applicable local, national and international codes, standards, regulations or industry
guidelines.
Values
Default
Min/Max:
Display:
A093 [Auto Rstrt Delay]
Sets the time between restart attempts when A092
Values
Default
Min/Max:
Display:
Stop drive before changing this parameter.
A094 [Start At PowerUp]
Enables/disables a feature that allows a Start or Run command to automatically cause the drive to
resume running at commanded speed after drive input power is restored. Requires a digital input
configured for Run or Start and a valid start contact.
This parameter will not function if parameter P036
ATTENTION: Equipment damage and/or personal injury may result if this parameter
is used in an inappropriate application. Do not use this function without considering
!
applicable local, national and international codes, standards, regulations or industry
guidelines.
Options 0 "Disabled" (Default)
1 "Enabled"
to a value other than "0".
to "0".
0
0/9
1
[Auto Rstrt Tries]
1.0 Secs
0.0/120.0 Secs
0.1 Secs
[Start Source]
Programming and Parameters
(continued)
Related Parameter(s):
is set to a value other than zero.
is set to 4 "2-Wire High Speed".
3-21
A092