A-2
Supplemental Drive Information
Specifications
Drive Ratings
Output Ratings
Catalog
Number
kW (HP)
100 - 115V AC 1-Phase Input, 0 - 230V 3-Phase Output
22A-V1P5N104 0.2 (0.25)
22A-V2P3N104 0.37 (0.5)
22A-V4P5N104 0.75 (1.0)
200 - 240V AC – 1-Phase
22A-A1P5N104 0.2 (0.25)
22A-A2P3N104 0.37 (0.5)
22A-A4P5N104 0.75 (1.0)
22A-A8P0N104 1.5 (2.0)
200 - 240V AC – 3-Phase Input, 0 - 230V 3-Phase Output
22A-B1P5N104 0.2 (0.25)
22A-B2P3N104 0.37 (0.5)
22A-B4P5N104 0.75 (1.0)
22A-B8P0N104 1.5 (2.0)
22A-B012N104 2.2 (3.0)
22A-B017N104 3.7 (5.0)
380 - 480V AC – 3-Phase Input, 0 - 460V 3-Phase Output
22A-D1P4N104 0.37 (0.5)
22A-D2P3N104 0.75 (1.0)
22A-D4P0N104 1.5 (2.0)
22A-D6P0N104 2.2 (3.0)
22A-D8P7N104 3.7 (5.0)
Input/Output Ratings
Output Frequency: 0-240 Hz (Programmable)
Efficiency: 97.5% (Typical)
Digital Control Inputs (Input Current = 6mA)
SRC (Source) Mode:
18-24V = ON
0-6V = OFF
Control Output
Programmable Output (form C relay)
Resistive Rating: 3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC
Inductive Rating: 0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC
Fuses and Circuit Breakers
Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Other Protective Devices: 140M-xxx (A-B Bulletin 140 Manual Motor Starter) or HMCP circuit breaker or equivalent.
Protective Features
Motor Protection: I 2 t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)
Overcurrent: 200% hardware limit, 300% instantaneous fault
Over Voltage:
100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)
200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)
380-480V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)
Under Voltage:
100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)
200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)
380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)
Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs
Faultless Power Ride Through: 100 milliseconds
Dynamic Braking
Internal brake IGBT included with all ratings 0.75 kW (1 HP) and larger. Refer to
options.
(1)
200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N104 to N114.
Input Ratings
Voltage
Amps
Range
kVA Amps Fuses
1.5
90-126
0.75 6.0
2.3
90-126
1.15 9.0
4.5
90-126
2.25 18.0
(1)
Input, 0 - 230V 3-Phase Output
1.5
180-265
0.75 5.0
2.3
180-265
1.15 6.0
4.5
180-265
2.25 10.0
8.0
180-265
4.0
1.5
180-265
0.75 1.8
2.3
180-265
1.15 2.5
4.5
180-265
2.25 5.2
8.0
180-265
4.0
12.0
180-265
5.5
17.5
180-265
8.6
1.4
340-528
1.4
2.3
340-528
2.3
4.0
340-528
4.0
6.0
340-528
5.9
8.7
340-528
8.6
SNK (Sink) Mode:
0-6V = ON
18-24V = OFF
Branch Circuit Protection
140M Motor
Protectors
10
140M-C2E-C10 100-C09
15
140M-C2E-C16 100-C12
30
140M-D8E-C20 100-C23
10
140M-C2E-B63 100-C09
10
140M-C2E-B63 100-C09
15
140M-C2E-C16 100-C12
18.0
30
140M-D8E-C20 100-C23
3
140M-C2E-B25 100-C09
6
140M-C2E-B40 100-C09
10
140M-C2E-C10 100-C09
9.5
15
140M-C2E-C16 100-C12
15.5
25
140M-C2E-C16 100-C16
21.0
35
140M-F8E-C25 100-C23
1.8
3
140M-C2E-B25 100-C09
3.2
6
140M-C2E-B40 100-C09
5.7
10
140M-C2E-B63 100-C09
7.5
15
140M-C2E-C10 100-C09
9.0
15
140M-C2E-C16 100-C16
Approvals
D
U L
UL508C
®
EMC Directive 89/336
LV:
EMC:
Analog Control Inputs
4-20mA Analog: 250 ohm input impedance
0-10V DC Analog: 100k ohm input impedance
External Pot: 1-10k ohms, 2 Watt minimum
page B-2
Power
Dissipation
IP20 Open
Contactors
Watts
25
30
50
25
30
50
80
25
30
50
80
115
165
30
40
60
90
145
D
U L
CSA 22.2
C
®
EN 50178, EN 60204
EN 61800-3, EN 50081-1, EN 50082-2
for external dynamic brake module