Advanced Program Group
A065 [Analog Out Sel]
Sets the analog output signal mode (0-10V, 0-20mA, or 4-20mA). The output is used to provide a
signal that is proportional to several drive conditions.
Output
Option
Range
0 "OutFreq 0-10"
0-10V
1 "OutCurr 0-10"
0-10V
2 "OutVolt 0-10"
0-10V
3 "OutPowr 0-10"
0-10V
4 "TstData 0-10"
0-10V
5 "OutFreq 0-20"
0-20mA
6 "OutCurr 0-20"
0-20mA
7 "OutVolt 0-20"
0-20mA
8 "OutPowr 0-20"
0-20mA
9 "TstData 0-20"
0-20mA
10 "OutFreq 4-20"
4-20mA
11 "OutCurr 4-20"
4-20mA
12 "OutVolt 4-20"
4-20mA
13 "OutPowr 4-20"
4-20mA
14 "TstData 4-20"
4-20mA
Values
Default
Min/Max:
Display:
A066 [Analog Out High]
Scales the Maximum Output Value for the A065 [Analog Out Sel] source setting.
Examples:
A066 Setting
A065 Setting
50%
1 "OutCurr 0-10"
90%
8 "OutPowr 0-20"
Values
Default
Min/Max:
Display:
Programming and Parameters
(continued)
Minimum Output
Maximum Output Value
Value
A066 [Analog Out High]
0V = 0 Hz
P035 [Maximum Freq]
0V = 0 Amps
200% Drive Rated Output Current
0V = 0 Volts
120% Drive Rated Output Volts
0V = 0 kW
200% Drive Rated Power
0V = 0000
65535 (Hex FFFF)
0 mA = 0 Hz
P035 [Maximum Freq]
0 mA = 0 Amps
200% Drive Rated Output Current
0 mA = 0 Volts
120% Drive Rated Output Volts
0 mA = 0 kW
200% Drive Rated Power
0 mA = 0000
65535 (Hex FFFF)
4 mA = 0 Hz
P035 [Maximum Freq]
4 mA = 0 Amps
200% Drive Rated Output Current
4 mA = 0 Volts
120% Drive Rated Output Volts
4 mA = 0 kW
200% Drive Rated Power
4 mA = 0000
65535 (Hex FFFF)
0
0/14
1
A065 Max. Output Value
5V for 200% Drive Rated Output Current
18mA for 200% Drive Rated Power
100%
0/800%
1%
Related Parameter(s): P035,
DIP Switch
Position
0-10V
0-10V
0-10V
0-10V
0-10V
0-20mA
0-20mA
0-20mA
0-20mA
0-20mA
0-20mA
0-20mA
0-20mA
0-20mA
0-20mA
Related Parameter(s):
3-19
A066
A065