Phase Shift When Closing (For Motor 1); Anti-Crushing Protection; Electric Lock; Fine Adjustment Of The Impact Forces (Combined With Par. 31 And 32) - Roger Technology B70-2DCHP Instrucciones Y Advertencias Para El Instalador

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 90
26 05

Phase shift when closing (for motor 1)

00
30
SECONDS
-
NOTE: parameter
27 03
Time taken to move back after the intervention of the safety edge or the anti-crushing protection
00
60
SECONDS
-
Establishes how many seconds the reversal operation on obstacle lasts; set to a value high enough
to reach the opening limit switch it also performs automatic reclosing according to parameter
29 01

Electric lock

00
DEACTIVATED
01
ENABLED
Activation occurs 0.5 seconds before the start of the movement and lasts 3 seconds.
The controller takes into account when door 1 is approaching the closure stop, and helps the electric
lock to hook. WARNING! For proper operation, adjust the mechanical stop inside the BR21 motor
carefully (see also Note
30 05

Fine adjustment of the impact forces (combined with par. 31 and 32)

motor torque reduction 1 = -8%, 2 = -6%, 3 = -4%, 4 = -2%
01
09
5 = the motor torque is at the factory setting
-
motor torque increase 6 = +2%, 7 = +4%, 8 = +6%, 9 = +8%
NOTE: increasing / decreasing the parameter increases / decreases the nominal torque of the
motors, and accordingly adjusts the force of impact. During the path program the controller stores
the consumption of current of the motors, and uses this information to always give a margin more
than what is needed for the actual path. However, this margin is reduced to 0 if you set parameter
30
01
to
. The value
affected by environmental effects such as strong winds or particularly cold weather.
ATTENTION! For gates with very different lengths, you can separately adjust the impact force: to do
this, you need to set par.
while the impact force of motor 2 adjusts using par.
31 15

Impact force level motor 1

32 15
Impact force level motor 2
01
10
low torque motor : 1 minimum impact force ... 10 maximum impact force
-
11
19
medium torque motor : 11 minimum impact force ... 19 maximum impact force
-
20
Maximun torque motor : without any adjustment of the anti-crushing protection
NOTE: parameter
In order to fall within the limits of impact forces, usually use the values from
to be performed at each installation. The values from
11-19
are not adequate. The value
Low and medium motor torque values can be set using parameter
31
32
and
separate adjustment is chosen for the two motors, also on par.
too long, reduce the value of parameter
4-
in simplified mode .
13
14
and
01
is therefore to be used only for particularly light installations that are not
33
at a different value than
9-
A-
and
in simplified mode
causes the impact to be too hard, try decreasing parameter
relating to the parameters).
10
33
.
01
20
should be used only in the presence of sensitive edges.
31
for door 1 (or parameter
30
. By doing so, par.
11
10
to
are to be used only in case the values
30
: if the setting of parameters
30
33
). If the reaction time is however
32
, for door 2).
49
.
only adjusts motor 1,
19
to
; the check is
(and, if necessary, if
37

Publicidad

Tabla de contenido
loading

Tabla de contenido