OFF2 S_src 1 (electrical)
p0844[C]
(1)
&
p0845[C]
(1)
OFF2 S_src 2 (electrical)
<1> STW1.10 must be set to ensure that the drive object accepts the
process data (PZD).
<2> PROFIBUS interconnection:
For the manufacturer-specific PROFIBUS telegram, the upper
input is connected to PROFIBUS signal E_STW1 [2447].
Only applies for CDS0.
<3> Is pre-defined via the PC if the master control is retrieved.
<4> Only for S120 and G150.
1
2
DO: B_INF
Basic Infeed - Control word, sequence control, infeed
Bit No.
p0840[C] (0)
<3>
0
0 = OFF1 (open precharging/line contactor)
1 = Operating condition no OFF2 (enable is possible)
1
0 = OFF2 (open precharging/line contactor and power-on inhibit)
2
Reserved
3
Reserved
4
Reserved
5
Reserved
6
Reserved
7
Reserved
8
Reserved
9
Reserved
p0854[C] (0)
<3>
10
1 = Control by PLC
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
3
4
Control word sequence control infeed
= CLOSE (close precharging/line contactor)
<1>
5
6
fp_8720_54_eng.vsd
09.11.18 V05.02.03
p0115[3]
<4>
STW seq ctrl
r0898
r0898.0
To the sequencer [8732]
r0898.1
To the sequencer [8732]
r0898.10
7
8
Function diagram
- 8720 -
S120/S150/G130/G150