Voltage
Current
V
I S5.0 [9566]
V
I S5.1
X521.3
S5.1
+
<1>
AI 1
-
X521.4
+/-20 mA
+/-10 V
TM31 AI inv S_src
p4067[1]
TM31 AI absVal act
p4066[1] (0)
0
1
<1> Differential input!
In case of a ground-based input signal, the terminal X521.4 must be connected to the reference potential M.
Caution:
The voltage between an input (X521.3 or X521.4) and the ground point must not exceed 35 V.
When the load resistor is switched in (S5.1 closed), the voltage between the input terminals must not exceed 15 V.
<2> For p4056 = 2, 3, 5 the units are mA.
For p4056 = 0, 4 the units are V.
1
2
DO: TM31
Terminal Module 31 (TM31) - Analog input 1 (AI 1)
<2>
TM31 AI Offset
Hardware
-20.000...20.000
smoothing
p4063[1] (0.000)
(100 µs)
+
A
+
D
(0)
TM31 AI T_smooth
0.0...1000.0 [ms]
p4053[1] (0.0)
0
x
-1
1
otherwise y = y(old)
3
4
<2>
<3>
TM31 AI type
p4056[1] (4)
20 mA
0
20 mA
1
<2> <3>
TM31 AI inp_U/I
0, 2
r4052[1]
3
0
0
4 mA
4, 5
1
TM31 AI sim setp
TM31 AI sim_mode
-20.000...20.000
p4097[1] (0)
p4098[1] (0.000)
TM31 AI enable
p4069[1]
(1)
TM31 AI window
0.0...20.0 [%]
p4068[1] (0.0)
0
0 %
y = x if
y
|y - x| > p4068
1
5
6
fp_9568_51_eng.vsd
04.06.19 V05.02.03
p4099[1] (4000.00 µs)
TM31 WireBrkThresh
0.00...20.00 [mA]
p4061[1] (2.00)
0...1000 [ms]
p4062[1] (100)
≠3
T
0
3
<2>
-20.000...20.000
-20.000...20.000
p4057[1] (0.000)
p4059[1] (10.000)
y
[%]
-1000.00...1000.00 [%]
y
p4060[1] (100.00)
2
x
x
1
-1000.00...1000.00 [%]
y
1
p4058[1] (0.00)
Scaling
Reference quantity
(e.g. p2000...r2004)
x
1
×
r4055[1]
x
2
x
x
1
2
100
%
<3> p4056
= 0: 0 V ... +10 V
= 2: 0 mA ... +20 mA
= 3: 4 mA ... +20 mA with monitoring
= 4: -10 V ... +10 V
= 5: -20 mA ... +20 mA
7
Function diagram
SINAMICS
<2>
[%]
y
x
x
2
y
8
- 9568 -