Missing enable signals
Missing enable signals prevent the infeed going into the state "operation"
(Operation enabled: r0899.2 = 1 [8926]).
Bit No.
Meaning
1 = OFF1 enable missing
0
(p0898.0 = 0 [8720] or switching on inhibited is present)
1
1 = OFF2 enable missing (p0898.1 = 0 [8720])
2...7
Reserved
1 = EP terminals enable missing
8
(pulse enable EP terminals missing)
9...15
Reserved
1 = OFF1 enable internal missing
16
(OFF1 fault response is present)
1 = OFF2 enable internal missing (commissioning selected
17
p0009 > 0 or p0010 > 0 or OFF2 fault response present)
18...25
Reserved
26
1 = Infeed inactive or not operational
27, 28
Reserved
29
1 = Cooling unit ready signal missing
30, 31
Reserved
<1> Only for S120 and G150.
1
2
DO: B_INF
Basic Infeed - Missing enable signals, line contactor control
Missing enable sig
r0046
r0046.0
[3020.5]
r0046.1
From sequencer [8732]
S7: Open
r0046.8
line contactor
S6: Open
line contactor
S3a: Close
line contactor
r0046.16
r0046.17
Line contactor
closed
r0899.12
r0046.26
r0046.29
3
4
p0115[3]
Control Unit
Line contactor control
Energize
contactor
r0863.1
[2130]...[2133]
Line contact feedb
p0860
(r0863.1)
[2120]...[2133]
ON/OFF monitoring
0...5000 [ms]
p0861 (100)
T
0
=1
≥1
Operation monitoring
5
6
fp_8738_54_eng.vsd
09.11.18 V05.02.03
<1>
From the line supply
DO
+24 V
DI
To the Line Module
7
8
Function diagram
- 8738 -
S120/S150/G130/G150