Mot t_de-excitat
0.000...20.000 [s]
p0347[M] (0.000)
<2>
ASC/DCBRK config
0...14
p1231[M] (0)
ASC/DCBRK act
<7>
p1230[C]
4,14
(0)
5
≥1
OFF1/OFF3
0
DC braking
not about BICO
DC braking fault response
4,5,14
OFF
0
<1> The DC brake current is determined during automatic calculation (p0340 = 1).
<2> The de-magnetization time is determined during automatic calculation (p0340 = 1, 3).
<3> As soon as the standstill threshold (p1226) has been reached, the DC current injection will be aborted prematurely.
<4> Signal r1239.8 is only set while the DC brake is active.
1
2
DO: SERVO, VECTOR
Technology functions - DC brake (p0300 = 1xx)
DCBRK I_brake
DCBRK time
DCBRK n_start
0.00...10000.00 [A]
0.0...3600.0 [s]
20.00...210000.00 [rpm]
p1232[M] (0.00)
p1233[M] (0.0)
p1234[M] (0.00)
<1>
n_act
Pulse inhibit
n_set
p1234
|I_set|
p0347
<3>
p1232
p1231 = 14
Braking response
n_act
Pulse inhibit
n_set
p1234
|I_set|
p0347
<3>
p1232
p1233
p1231 = 5
n_act
Pulse inhibit
BICO = 1
BICO = 0
n_set
t
|I_set|
p0347
p1232
p1231 = 4
3
4
I_act abs val
r0068[0]
To pulse inhibit
The parameters of the I_max current controller are also used.
To sequencer
I_max_U_ctrl Kp
DC braking ready
0.000...100000.000
r1239.10
p1345[D] (0.000)
|I_set|
–
MIN
From I2t control
+
[8021]
DC braking active
r1239.8
<4>
<5> Only for SINAMICS S120 and SERVO.
<6> Only for SINAMICS S120 and VECTOR.
<7> DC brake upon falling below the starting speed for DC brake (p1234).
5
6
fp_7017_54_eng.vsd
07.04.17 V05.02.03
p0115[0]
I_max_U_ctrl Tn
0.000...50.000 [s]
p1346D] (0.030)
U_output
r0072
Kp
Tn
To control
[5730] <5>
[6730] <6>
To U/f-characteristic [6300] <6>
7
8
Function diagram
- 7017 -
S120/S150/G130/G150