Commissioning And Operation; Making Settings; Setting The Baud Rate - Aventics CANopen Instrucciones De Servicio

Acoplador de bus bdc, diseño b
Ocultar thumbs Ver también para CANopen:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 233
82
AVENTICS | CANopen, CANopen sb | R412009415–BDL–001–AE

Commissioning and operation

A
B
7
Commissioning and
operation
7.1

Making settings

The following presettings have to be made:
W
Setting the bus coupler address
W
Select the valve supply
W

Setting the baud rate

W
Setting the diagnostic messages.
All of these settings are made using the switch beneath
fittings A and B.
Proceed as follows for all of the presettings:
1.
Remove the corresponding fittings.
2.
Adjust the corresponding setting as described below.
3.
Screw the fittings back in (0.6 + 0.2 Nm). Pay
attention that the sealing rings are positioned
correctly.
7.1.1
Setting the baud rate
The baud rate is set on switch S3 (see Tab. 10 on page 82).
It is located under fitting B.
1.
Open fitting B.
2.
Set the baud rate (transfer rate) with the S3.1 to S3.3
switches in accordance with the information listed in
Tab. 10 on page 82.
Default setting: 1 MBaud
Table 10:
S3, Switch assignments for baud rate setting
Baud rate
Max. line length
1)
1 Mbit/s
25 m
Reserved
500 kbit/s
100 m
250 kbit/s
250 m
125 kbit/s
500 m
50 kbit/s
1 km
20 kbit/s
2.5 km
10 kbit/s
5 km
1)
Default settings
S3.3
S3.2
S3.1
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Canopen sb

Tabla de contenido