Setting The Bus Coupler Address; Setting The Diagnostic Messages - Aventics CANopen Instrucciones De Servicio

Acoplador de bus bdc, diseño b
Ocultar thumbs Ver también para CANopen:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 233
AVENTICS | CANopen, CANopen sb | R412009415–BDL–001–AE
7.1.2
The station address is set using the S1 and S2 switches
(see Fig. 8).
Fig. 8:
Both S1 and S2 rotary switches for the valve system
station address in the CANopen are located beneath the
PG fitting A.
O
Assign the station address freely from 1 to 99 using
S1 and S2 (see Fig. 8).
– S1: Unit digits from 0 to 9
– S2: Tens digits from 0 to 9
– S1 + S2 = station address
Default setting: node ID = 2
The entered address is newly read when the bus coupler
is started (power on). Changing the address during
operation will therefore only take effect after one of the
events mentioned.
Do not use address 0, it causes a system stop.
7.1.3
The S3 mode switch used to set the diagnostic messages
is located under the PG fitting A (see Fig. 8 on page 83).
The system is CANopen conform on delivery.
Diagnosis is deactivated (S3.5 set to OFF).
Commissioning and operation

Setting the bus coupler address

S2
S1
S1, S2 address switches and S3 mode switch
on the bus coupler

Setting the diagnostic messages

83
S3