7.4.15 DR Function – Data Register
The DR function enables the DR internal register, allowing the transfer of a value to this
register while the function is enabled. CLICK-02 has a total of 240 DR registers. The registers
can be set to store data without signal (0 ~ 65535) or with signal (-32768 ~ 32767), this
operation is set in the system configurations by the CLICK-02 programming software (menu
Operation>> System Configuration).
On the CLIC02- display, or in the programming tool, the DR function will be shown as follows:
The data registers from DR65 to DRF0 are retentive, ie, they maintain their value when
the equipment is de-energized. The last 40 DRs (DRC9 to DRF0) are special registers, as
shown below:
DRC9
PLSY total number
DRCA~DRCF
Reserved
DRD0
Output mode AQ01
DRD1
Output mode AQ02
DRD2
Output mode AQ03
DRD3
Output mode AQ04
DRD4~DRF0
Reserved
- English -
Symbol
Register number: DR01 ~ DRF0
Value transferred to the DR
With signal: -32768 ~ 32767
Without signal: 0 ~ 65535
(1) The Set-Points can be constant or current values of
any other function.
Ladder Logic Programming
Description
register
(1)