7 LADDER LOGIC PROGRAMMING
7.1 DIGITAL VARIABLES
Digital Input
Digital Output
Input via Keyboard
Expansion Digital Input
Expansion Digital Output
Auxiliary Marker
Timer
Counter
RTC
Comparator

7.1.1 Digital Inputs

For the points of CLIC-02 digital input, variables type I are associated. The maximum number
of digital input points I varies according to CLIC-02 model, reaching up to 12 points – I01 ~I0C.
The expansion digital inputs are assigned by the X variable, in the range of X01 ~ X0C.

7.1.2 Digital Outputs

For the digital output points of CLIC-02, variables Q are assigned. The number of digital output
points Q varies according to the CLIC-02 model, reaching up to 8 points – Q01 ~ Q08. For
expansion digital outputs, variables Y-Y01 ~Y0C are associated. In this example, the output
point Q01 will be connected when the input point I01 is activated.
When CLIC-02 model has less digital outputs, remaining variables Q may be used as
auxiliary markers, increasing even more CLIC-02 capacity.
Contacts
Symbol
/
I
I / i
Q
Q / q
Z
Z / z
X
X / x
Y
Y / y
M
M / m
N
N / n
T
T / t
C
C / c
R
R / r
G
G / g
- English -
Ladder Logic Programming
Quantity
Valid Range
12
I01 ~ I0C
8
Q01 ~ Q08
4
Z01 ~ Z04
12
X01 ~ X0C
12
Y01 ~ Y0C
63
M01 ~ M3F
63
N01 ~ N3F
31
T01 ~ T1F
31
C01 ~ C1F
31
R01 ~ R1F
31
G01 ~ G1F