WEG CLIC-02 Manual Del Usuario página 151

Microcontrolador programable
Ocultar thumbs Ver también para CLIC-02:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

The standard configuration for the port RS-485 of CLIC-02 is shown in the table below:
The communication port RS-485 parameters are adjustable only in the CLIC-02 versions 3.x;
After changing the communication port RS-485 parameters, it is required to restart
CLIC-02
10.2 REMOTE I/O FUNCTION
Up to 2 CLIC-02 units can be set for the Remote I/O mode, one as a master and the other
as a slave. Master CLIC-02 will execute its program, reading the inputs and powering the
outputs of the slave CLIC-02. The Slave CLIC-02 will not execute its program, all its inputs/
outputs will depend on Master CLIC-02. For powering the slave outputs Q, the master will
operate on the variables Y in its program. The slave inputs I will be written on the master
variables X. Therefore, no I/O expansion can be used in both the slave and the master.
Input coil
Output Coils
Expansion Input Coils
Expansion Output Coils
Hardware Configuration:
1. Connect the CLIC-02 unities through the port RS-485, following the installation
instructions of the item 4.4.7.
2. Adjust the left CLIC-02 on the illustration to Master.
3. Adjust the other CLIC-02 to Slave.
Baud Rate
Data bit
Bit Stop
Parity
Telegram Maximum Size
I/O Address
Master
- English -
Port RS-485 Communication Functions
38400bps
8
2
No
128 bytes
Master
Slave
I01 ~ I0C
Q01 ~ Q08
X01 ~ X0C
I01 ~ I0C
Y01 ~ Y0C
Q01 ~ Q08
RS-485
Slave
CLIC-02 | 151