WEG CLIC-02 Manual Del Usuario página 178

Microcontrolador programable
Ocultar thumbs Ver también para CLIC-02:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Expansion Modules
Stop Bit and Parity
To set the number of Stop Bits and the Parity check, see table below. The switches SW1.7
and SW1.8 are reserved.
SW1.6
SW1.5
OFF
*
OFF
OFF
OFF
ON
ON
*
* irrelevant condition
Status Indication and Error Codes
Error
Status
code
Indication
56H
Error LED
The connection between
flashes
the CLIC-02 is improper.
slowly
(2Hz)
55H
Error LED
CLIC-02 configuration
keeps
error: configuration in the
ON
"I/O Number" is different
from the actual one.
51H,
Error LED
Modbus request error:
54H
flashes
Data telegram, function
slowly
code, record address,
(2Hz)
CRC, error check, etc.
59H
Error LED
Data error in
flashes
communication: Error Bit
quickly
check
(5Hz)
Data length of the error
response, CRC error
For further information, see Chapter 10: Communication Functions of the Port RS-485;
11.4.2 Communication Module DeviceNet
Summary
The module CLIC-02/DNET is a DeviceNet communication interface, which enables the
CLIC-02 as a network slave equipment, allowing control and remote monitoring via a
DeviceNet master.
178 | CLIC-02
SW1.4
OFF
2 Stop Bits, No Parity
ON
1 Stop Bit, Odd Parity
ON
1 Stop Bit, Even Parity
*
Adjust the port to the factory standard: 38,4 Kbps,
2 Stop Bits, No Parity
Error type and
possible cause
- English -
Condição
Solution
Check the connection
between CLIC-02,
I/O modules and
communication modules.
Check the CLIC-02
configuration.
Check the order and
configuration of the
communication in
accordance with the
protocol.
Ensure that the connection
between the CLIC-02
and the Communication
Module is reliable; check
possible noises generated
by equipment installed in the
surroundings.
Observation
The expansion
modules that
precede the
communication
module may be
causing this failure