WEG CLIC-02 Manual Del Usuario página 88

Microcontrolador programable
Ocultar thumbs Ver también para CLIC-02:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Ladder Logic Programming
In the example below counter C02 will check the fast input I02 frequency. The scan cycle is
programmed to 0.1s. At each completed scan cycle, counter C02 will compare the number
of pulses counted in this cycle with the programmed range, which is from 3 to 5 pulses to
turn on. Note that the output is enabled when the current value is higher than or equal to
the lower limit of the comparison range and lower than the upper limit.
Counting preset
Preset de contagem
Counting pulse
Pulso de contagem
Counter output
Saída do contador
7.4.3 Real Time Clock - RTC
CLIC-02 has 31 RTC comparison instructions; each one can operate in 5 comparison
modes. Each RTC comparison instruction has 10 parameters for configuration. The
RTC comparison instructions are addressed by the mnemonic R, available in the range
R01 ~R1F. The comparison instructions will actuate according to the CLIC-02 real time
clock, which can be adjusted through CLIC-02 display or by the programming tool.
7.4.3.1 RTC Mode 0 – Auxiliary Marker
When a comparison instruction is configured to mode 0 it will work as an internal auxiliary
marker M or N. The other configuration parameters will keep disabled when this mode is
selected.
I01
OFF
R01
OFF
88 | CLIC-02
OFF
ON
OFF
ON
OFF
- English -
ON
OFF
ON
OFF
ON
OFF

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido