WEG CLIC-02 Manual Del Usuario página 182

Microcontrolador programable
Ocultar thumbs Ver también para CLIC-02:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Expansion Modules
Connection to the Profibus DP Network
When using a 9-pin connector to connect to the PROFIBUS DP busbar, please use regulated
connectors and cables.
Port Signals
Number
1
Reserved
2
Reserved
3
RxD/TxD-P (Line B)
4
Reserved
5
DGND (2M)
6
VP(2 P5)
7
Reserved
8
RxD/TxD-N (Line A)
9
Reserved
Baud Rate Configuration and Device Address
During the startup of the CLIC-02/PBUS the identification of the Baud Rate and the Profibus
network occurs, which will be authenticated if the master is in the Baud Rate range allowed
by CLIC-02/PBUS, which ranges between 9.6 kbits and 6 kbits. Each slave must have a
different ID, from 0 to 126. The CLIC-02/PBUS ID is adjusted by the switches SW1, as
shown below:
SW1.7
SW1.6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
-
-
ON
ON
ON
ON
The eighth bit is reserved.
182 | CLIC-02
Name
SW1.5
SW1.4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
-
-
ON
ON
ON
ON
- English -
Description
Send/Receive data (positive)
Digital GND
+5VDC (expansion of the supply busbar)
Send/Receive data (negative)
SW1.3
SW1.2
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
-
-
ON
OFF
ON
ON
SW1.1
ID
OFF
0
ON
1
OFF
2
ON
3
OFF
4
-
-
ON
125
OFF
126

Publicidad

Capítulos

Tabla de contenido