10.5.2.2 Status/Control Variables of the CLIC-02
Modbus address
Decimal Hexadecimal
256
0100H
257
0101H
258
0102H
259
0103
260
0104
261
0105
262
0106
263
0107
264
0108
265
0109
266
010A
267
010B
Supported
Functions
03H
06H
RUN / STOP:
10H
CLIC-02 Model (hexadecimal code):
03H
30=20VR-D,
34=20VT-D,
Word Status 1:
Bit 0 and 1 – RS-485 Communication Mode
0: Datalink
1: Remote I/O – Master
2: Remote I/O - Slave
Bit 4 - Backlight
0: Automatic – Off after Inactivity Period
1: Always On
Bit 5 – Retentive Counter
1: Retentive
0: Non-Retentive
Bit 6 – Configuration of Retentive M Markers
1: Non-Retentive
03H
0: Retentive
06H
Bit 8, 9, 10 and 11 – Seleted Language
10H
1: English
2: French
3: Spanish
4: Italian
5: German
6: Portuguese
7: Chinese
Bit 12 and 13 – Number of set expansions (0 ~ 3)
Bit 14 – Configuration of Z keys
0: Disabled Z keys
1: Enabled Z keys
Bit 15 – Alarm Expansion N° different from the set one
0: Alarm
1: With alarm
Word Status 2:
Low-Byte – Error Code
0 = OK
1 = Rom Error
2 = RAM Error
3 = EEPROM Error
4 = Program Error
5 = Program Logic Error
03H
6 = Watchdog Error
7 = Expansion Errors
8 = Communication Error
9 = RTC Error
High Byte – Password Configuration
0 = Disabled Password
1 = Enabled Password
Analog Input 1 Gain
Analog Input 1 Offset
Analog Input 2 Gain
Analog Input 2 Offset
03H
10H
Analog Input 3 Gain
Analog Input 3 Offset
Analog Input 4 Gain
Analog Input 4 Offset