Expansion Modules
Baud Rate Address and Configuration
On the DeviceNet network, each slave needs a different ID, seeing that the valid ID
range is from 0 to 63. The slave address is adjusted by the switches SW1.1 ~ SW1.6 of
the CLIC-02/DNET module. The communication Baud Rate is adjusted by the switches
SW1.7 and SW1.8. The adjusted Baud Rate and the DeviceNet master must be the same.
Adjustment of the switches SW1
Address
SW1.6 ~ SW1.1
Baud Rate
SW1.8 ~ SW1.7

Status LED

The CLIC-02/DNET has 2 LEDs, one for an internal diagnosis and the other for the busbar
status of the communication network.
1. Module Status LED (MS)
Dual color LED (green and red) indicates the status of the CLIC-02/DNET.
LED Status (MS)
Off
No supply
Green On
Standard Operating Status
Green Flashing
Not connected to the basic unity
CLIC-02
Red Flashing
Connected to CLIC-02, but there is
communication error between the
modules
Red On
Hardware error in the module
180 | CLIC-02
000000
000001
......
111110
111111
00
01
10
11
Explanation
- English -
ID: 0
ID: 1
......
ID: 62
ID: 63
Baud Rate: 125K
Baud Rate: 250K
Baud Rate: 500K
Standby (Standard Baud Rate): (125K)
Failure Correction or Prevention
Connect to a power supply
-
Connect to CLIC-02 properly
Set the CLIC-02 I/O Number properly
Replace module